Boiler Water Circulating Pump Motor Repair – Practical Field Guide

Boiler water circulating pump motors are critical equipment. Any repair must be done systematically to avoid repeat failures and boiler trips.

1. Common Motor Problems

✔ Motor not starting
✔ High current / tripping
✔ Overheating
✔ Abnormal noise / vibration
✔ Low insulation resistance
✔ Bearing failure
✔ Moisture ingress


2. Step-by-Step Repair Procedure

A. Initial Inspection (At Site / Workshop)

☐ Record nameplate details (kW, V, A, RPM, Insulation class)
☐ Check external damage & terminal box
☐ Measure IR (Phase–Phase & Phase–Earth)
☐ Measure winding resistance balance
☐ Check earthing
☐ Inspect coupling & alignment


B. Electrical Fault Repair

1. Low IR / Earth Fault

  • Dry motor in oven or by space heater
  • Clean winding surface
  • Re-varnish if insulation is weak

2. Phase to Phase Fault

  • Rewinding mandatory
  • Upgrade insulation to Class H
  • Improve end winding bracing

3. High Current / Unbalance

  • Check supply voltage unbalance
  • Inspect winding symmetry
  • Verify correct Star/Delta connection

C. Mechanical Repair

Bearing Failure

☐ Replace bearings (recommended for boiler pumps)
☐ Check bearing housing wear
☐ Use high-temperature grease
☐ Maintain correct axial clearance

Vibration / Noise

☐ Rotor dynamic balancing
☐ Shaft run-out check
☐ Proper alignment with pump
☐ Check fan & cooling ducts


D. Rewinding Repair (If Required)

☐ Record original winding data
☐ Controlled stripping (≤ 350°C)
☐ Use Class F/H insulation materials
☐ Tight end-winding lacing
☐ VPI or double dip–bake impregnation
☐ HV, IR, PI testing after rewinding


3. Post-Repair Testing Checklist

☐ IR value satisfactory
☐ PI value ≥ acceptable limit
☐ HV test passed
☐ No-load current within limit
☐ Temperature rise normal
☐ No abnormal noise or vibration


4. Common Causes of Repeated Failures

❌ Poor alignment
❌ Boiler water leakage on motor
❌ Poor ventilation
❌ Inferior rewinding materials
❌ Running pump in cavitation
❌ Continuous overload


5. Preventive Actions (Highly Recommended)

✔ Install RTD/PTC temperature sensors
✔ Regular IR testing
✔ Maintain pump alignment
✔ Ensure proper ventilation
✔ Upgrade insulation during rewinding
✔ Avoid dry running


6. When to Repair vs Replace?

ConditionAction
Minor insulation issueRepair
Bearing failure onlyRepair
Burnt windingRewind
Core damageReplace motor
Multiple rewindsReplace

⭐ Expert Tip

For boiler circulating pumps, motor failure = boiler shutdown.
Always prioritize quality repair over cost saving.